Modbus/TCP

Modbus/TCP is the most widely deployed industrial protocol, running over TCP/502. It is a simple request-response protocol originally designed by Modicon (now Schneider Electric) in 1979 for serial communication, later adapted for TCP.

What IndustrialScanner does

The Modbus scanner issues only read function codes:

Code Name Description
0x01 Read Coils Read discrete outputs (ON/OFF)
0x02 Read Discrete Inputs Read discrete inputs (read-only)
0x03 Read Holding Registers Read 16-bit registers
0x04 Read Input Registers Read 16-bit input registers (read-only)

No write or control operations are intentionally issued. Read-only does not guarantee zero operational impact: validate the scanner in a representative lab, obtain asset-owner authorization, and use a maintenance window before active scanning of production PLCs.

Usage

industrial-scanner modbus --targets 192.168.1.10 --unit 1
industrial-scanner modbus --targets 192.168.1.0/24 --port 502 --unit 1
industrial-scanner modbus --targets @targets.txt --timeout 2.5

Output

Each scan produces:

  • JSON report in reports/modbus_batch/modbus_scan_<timestamp>.json
  • HTML report in reports/modbus_batch/modbus_scan_<timestamp>.html

The report includes:

  • Per-host: reachable, latency_ms, reads (4 windows), exposure flags, errors
  • Summary: total reachable, unauthenticated_read count, broad_register_access count

Exposure signals

The scanner reports two exposure signals per host:

  • unauthenticated_read: True if any read function returned data without authentication. Modbus/TCP has no built-in authentication, so this is almost always True for any reachable PLC.
  • broad_register_access: True if 2 or more read windows returned data. This indicates the PLC exposes multiple data types without restriction.

Security considerations

  • Modbus/TCP has no authentication, no encryption, no integrity by design
  • Anyone with network access to TCP/502 can read AND write to the PLC
  • The scanner is read-only, but a malicious actor on the same network is not
  • Active reads can still consume device or network resources; execution is single-flight by default and supports a delay between targets
  • For production deployments, consider Modbus/TCP Security (RFC 9441) which adds TLS + X.509 + per-function-code access control

MITRE ATT&CK mapping

Read operations map to: - T0801 — Monitor Process State - T0802 — Automated Discovery

(Write/control operations — if detected in passive PCAPs — map to T0858 Change Operating Mode. The scanner does not issue these.)