Siemens S7Comm

S7Comm is the proprietary protocol used by Siemens S7-300, S7-400, S7-1200, and S7-1500 PLCs. It runs over TCP/102 and is layered:

[TPKT header 4B][COTP header 3-17B][S7 header 10B][Parameter][Data]
  • TPKT (RFC 1006): wraps ISO transport over TCP
  • COTP (ISO 8073): ISO transport class 0
  • S7: Siemens application layer

What IndustrialScanner does

The S7Comm analyzer:

  1. Reads PCAP/PCAPNG files
  2. Filters TCP traffic on port 102
  3. Unwraps TPKT/COTP framing
  4. Parses the S7 header (byte 0 = 0x32 magic, byte 1 = ROSCTR)
  5. Parses the parameter block (function code at offset 10)
  6. Classifies each packet by function code
  7. Flags suspect functions (WriteVar, Start, Stop, DownloadBlock, CopyRamToRom, FirmwareUpdate, Password)
  8. Enriches with MITRE ATT&CK for ICS techniques

Function codes detected

Code Name Suspect Description
0x04 ReadVar No Read variables
0x05 WriteVar Yes Write variables
0x28 Start Yes Start CPU
0x29 Stop Yes Stop CPU
0xF0 SetupComm No Setup communication handshake
0x3A DownloadBlock Yes Download block to PLC
0x3B UploadBlock No Upload block from PLC
0x3C DeleteBlock Yes Delete block
0x44 FirmwareUpdate Yes Update firmware
0x45 Password Yes Authentication
0x46 ReadDiag No Read diagnostic data
0x4E CopyRamToRom Yes Persist RAM to ROM

Usage

# Analyze a single PCAP
industrial-scanner s7 --pcap capture.pcapng

# Batch process all PCAPs in pcaps/s7/
python -m s7_comm_analyzer.s7_analyze

Output

  • JSON report in reports/s7_batch/<basename>.json
  • HTML report in reports/s7_batch/<basename>.html

Each packet entry includes:

  • src, dst, function_code, length, hints (ASCII strings found in payload)
  • rosctr (Job, Ack, AckData, Userdata)
  • pdu_ref (PDU reference number)
  • mitre_attack (list of MITRE techniques)

Limitations

  • S7Comm-Plus (firmware ≥ V3.0 on S7-1200/1500) uses encrypted X3.1324 framing and is not supported. The analyzer will return NonS7Payload for these frames.
  • The parser does not yet decode the item structure within the parameter block (variable addresses, data types). Only the function code is extracted.

Security considerations

  • S7Comm has no authentication by default (the 0x45 Password function is optional and rarely used)
  • Anyone with network access to TCP/102 can issue Start/Stop/DownloadBlock
  • For production, use S7Comm-Plus (encrypted) or restrict TCP/102 access via firewall rules